The Model 520 is an Automatic Engine Control Module designed to automatically start and stop the engine. It will indicate the operational status and fault conditions, automatically shut down the engine and indicate the engine failure by a flashing LED on the front panel. Other simultaneous faults are indicated by steady LED. Selected operational sequences, timers and alarms can be altered by the customer by using either the 807 hand held calibration unit or a PC and the 808 interface. This also provides the operator with ‘real-time’ diagnostic facilities to monitor the operation of the system either locally or remotely. Remote PC-controlled engine starting and stopping is also featured. Operation of the module is via a three position rotary switch (key-switch option available) mounted on the front panel with STOP, AUTO and MANUAL positions. Microprocessor control allows for enhanced operation. The module features a comprehensive list of timers and pre-configured sequences. This allows complex specifications to be achievedConfigurable expansion facilities are provided.
CONFIGURABLE INPUTSConfigurable inputs are available for:- Low Oil Pressure
- High Engine Temperature
- Remote Start.
This allows the module to function with normally open or normally closed switches. Four fully configurable auxiliary inputs are provided to give protection expansion.These can be selected to be indication, warning or shutdown inputs either immediate or held off during start up.
ALARM CHANNELSMultiple alarm channels are provided to monitor the following:- Under/Overspeed
- Charge Fail
- Emergency Stop
- Low oil pressure
- High engine temperature
- Fail to Start
- Fail to stop
- Loss of speed sensing
- Programmable inputs as selected
First up alarm is indicated by a flashing LED. Subsequent simultaneous alarms are displayed by a steady LED.
Specification DC SUPPLY CONTINUOUS VOLTAGE RATING8 to 35 V Continuous.
CRANKING DROPOUTSAble to survive 0 V for 50 mS,providing supply was at least 10 Vbefore dropout and supply recoversto 5V. This is achieved without theneed for internal batteries.
MAXIMUM OPERATING CURRENT290 mA at 12 V. 210 mA at 24 V.
MAXIMUM STANDY CURRENT50 mA at 12 V. 30 mA at 24 V.
CHARGE FAIL EXCITATION RANGE0 V to 35 V
INPUTS ARTERNATOR INPUT RANGE15 - 300 V ac RMS
ALTERNATOR INPUT FREQUENCY50 - 60 Hz at rated engine speed.Magnetic Input Range:0.5 V to +/- 70 V (Clamped by transient suppressors)
MAGNETIC iNPUT FREQUENCY10Hz to 10,000 Hz
OUTPUTS START RELAY OUTPUT16 Amp DC at supply voltage.
FUEL RELAY OUTPUT16 Amp DC at supply voltage.
AUXILLIARY RELAY OUTPUTS5 Amp DC at supply voltage.
DIMENSIONSOVERALL 72 X 144 X 118.5 mm (Excluding switch)
Package include:- 1 x BC520A Generator Controller Board